Under the regulations of the Saudi Directorate General of Civil Defense and international NFPA 80 standards, all commercial buildings, hospitals, logistics warehouses, and shopping centers across the Kingdom must conduct and document an Annual Fire Shutter Drop Test. Fire-rated rolling shutters (rated for 120 to 240 minutes) act as critical compartmentalization barriers that halt toxic smoke and flames during building fires.
Key Steps of the NFPA 80 Drop Test Protocol
- Fusible Link & Thermal Release Audit: Inspect heat-sensitive eutectic fusible links designed to melt at 74°C (165°F) and trigger mechanical release.
- First Drop Test (Gravity Descent Speed): Disengage motorized brakes to confirm gravity descent speed operates between 150mm/sec and 600mm/sec governed by internal centrifugal brakes.
- Floor Contact & Latch Verification: Ensure bottom flame baffle bar seals 100% flush against concrete floor with zero light gaps.
- Reset & Second Drop Test: Manually reset tension springs and test automated release via Fire Alarm Control Panel (FACP) relay signal.